Eliwell Sb655 C Manual 2021 -

Complete Guide to the Eliwell SB655 C Controller: Operation, Configuration, and Troubleshooting

: Press the SET key once to see the current setpoint; press again to see the value. eliwell sb655 c manual

| Parameter | Description | Typical Refrigerator (0-5°C) | Typical Freezer (-18°C) | | :--- | :--- | :--- | :--- | | | Compressor differential (hysteresis). The compressor stops at SP and restarts at SP + c1. | 2.0°C | 3.0°C | | c2 | Compressor protection delay (anti-short cycle). Minimum time between stops and restarts. | 3 minutes | 4 minutes | | c3 | Probe display offset. Calibrates if the reading is wrong. | 0.0 | 0.0 | | c4 | Defrost interval (in hours). | 6 hours | 8 hours | | c5 | Defrost duration (in minutes). | 20 minutes | 30 minutes | | c6 | Defrost type: 0 = Electrical (Heater), 1 = Hot gas/Off-cycle. | 1 (Off-cycle) | 0 (Electrical) | | c7 | Drip time after defrost (minutes). | 2 min | 5 min | | AL1 | Low temperature alarm threshold (relative to setpoint). | -2.0°C | -22.0°C | | AL2 | High temperature alarm threshold (relative to setpoint). | +4.0°C | +10.0°C | | ALd | Alarm delay (minutes before sounding). | 60 min | 60 min | | F3 | Temperature unit: 0 = °C, 1 = °F. | 0 | 0 | Complete Guide to the Eliwell SB655 C Controller: